Appleton EYSM50 Conduit Sealing Fitting
Appleton EYSM50 Conduit Sealing Fitting
Part Number # EYSM50
SKU # 2250381
$27.20 / Each
$30.06/Each
Appleton EYSM50 Key Features
Brand: Appleton
Dimensions: 3.25 in L x 1.13 in W
Finish: Triple Coated
Series: EYSM
Size: 1/2, 1/2 in
Suitable For Use With: IMC/Threaded Rigid Metallic Conduit
Type: Dust-Ignitionproof Explosionproof Raintight
Country of origin: MX
Material: Malleable Iron
Manufacturer Name: Emerson Electric
UNSPSC: 39121311
UPC: 00781381331357
$27.20 / Each
$30.06/Each
Appleton EYSM50 Conduit Sealing Fitting
Brand: Appleton
Part Number: EYSM50
Appleton UNILETS Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EYSM, 1/2 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 3.25 in L x 1.13 in W
Additional Description: APLE-EYSM50 1/2 EYSF SERIES SEAL UNI
Catalog Description: UNILETS EYS Series 25 PCT Fill Vertical Conduit Sealing Fitting With Removable Nipple, Size: 1/2 IN, Material: Malleable Iron, Finish: Triple-Coat (Zinc Electroplate, Chromate And Epoxy Powder Coat), Connection: Tapered MNPT X Tapered FNPT
ApplicationFor prevent passage of gases, vapors or flames from one portion of conduit system to anotherItem Features- Smooth, rounded integral bushing in each hub to protect conductor insulation
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
- Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
- Large opening for damming and filling
- Restrict any explosion to the sealed off enclosure
- Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
- Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
- Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
- Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
- Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
- Tapered FNPT connection
- 25% fill vertical conduit sealing fittings
- Chromate/epoxy powder coated/zinc electroplated finish
StandardsARRA Compliant|UL 1203 File No. E10444|CSA 065181 C22.2 No. 30SKU #2250381Part Number #EYSM50UNSPSC39121311UPC00781381331357