Schneider Electric LC1D32BL Tesys D Iec Contactor
Schneider Electric Square D TeSys D IEC Contactor, Direct On-Line, Series: LC1D, 24/690 VAC, 300 VDC Coil, 32/50 A Maximum Load Current, 2.4 W Coil, 3 Pole, 50/60 Hz Frequency, 2/5 W Wattage, 3NO Contact Configuration, 1NO-1NC Auxiliary Contacts, 10/60 A at 575 VAC, 50/60 A at 575 VAC Contact, Screw Clamp Connection, 101/45/85 mm Size, Screw Clamp Terminal, Open Enclosure, 3600 cycles/hr Operating Cycles, -5 to 60/-40 to 70 deg C Operating, Rail/Surface Mounting, 45 mm W x 101 mm D x 85 mm H Dim
Additional Description: SQD -LC1D32BL TeSys 3P CTR 32A AC3 15KW 1NO1NC24VDC LC +OPTIONS
Catalog Description: IEC contactor, TeSys Deca, nonreversing, 32A, 20HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, low consumption 24VDC coil
LC1D32BL Application
For motor control and resistive loadsLC1D32BL Item Features
- 6 kV conforming to IEC 60947 rated impulse withstand voltage
- III overvoltage category
- 50 A at 140 deg F power circuit, 10 A at 140 deg F signaling circuit conventional-free air thermal current
- 550 A at 440 V power circuit conforming to IEC 60947, 140 A AC signaling circuit conforming to IEC 60947-5 1, 250 A DC signaling circuit conforming to IEC 60947-5 1 IRMS rated making capacity
- 550 A at 440 V power circuit conforming to IEC 60947 rated breaking capacity
- 63 A gG at 690 VAC coordination type 2 power circuit/63 A gG at 690 VAC coordination Type 1 power circuit/10 A gG signaling circuit conforming to IEC 60947-5-1 associated fuse rating
- 2 MOhm at 50 Hz, Ith 25 A power circuit average impedance
- 65.45 to 88.55 ms closing and 20 to 30 ms opening operating time
- 3600 cycles/hr at 140 deg F operating rate
- Built-in bi-directional peak limiting diode suppressor coil technology
- 40 ms time constant
- 2.4 W at 68 deg F inrush power
- 2.4 W at 68 deg F hold-in power consumption
- 25 to 400 Hz signaling circuit frequency
- 5 mA minimum switching current
- 17 VAC signaling circuit minimum switching voltage
- 1.5 ms on energization between NC and NO contact/1.5 ms on de-energization between NC and NO contact non-overlap time
- >10 MOhm signaling circuit insulation-resistance
- TH protective treatment
- 3 deg of pollution, 9842.52 ft (3000 m) without derating in temperature operating altitude
- https://www.youtube.com/embed/e8UrRZljFg0
LC1D32BL Standards
BV/GL//RINA Certified|CCC Certified|CE Certified|CSA C22.2 File No. 14 File No. LR43364 Class 3211 04|DNV/GOST Approved|ECCN EAR99|EN 60947-4-1/60947-5-1|IEC 60647-4/60947-4-1/60947-5-1|PROP65: This product can expose you to chemicals including: Antimony oxide and Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65warnings.ca.gov|RoHS Compliant|UL File No. E164862 NLDX/508SKU #618370Part Number #LC1D32BLUNSPSC39121529UPC00785901549512